52
Central Station Terms
Communicator Automated Programming Locations
Central Station Number: Space is provided for two 16-digit phone numbers. These numbers are programmed as
normally dialed. To enter communicator phone numbers, enter the appropriate 9000
location and enter the number. The system places the numbers in the appropriate
locations. There are characters that are available in the dialing string that are not found
on the keypad. The chart below explains how to enter additional functions:
Dialing Feature # or H Followed By
Dial * 1
Dial # 2
Wait for second dial tone 3
3 second pause in dialing sequence 4
After the number is entered, press # or H key twice to save. Pressing the * or A key at
any time during phone number will clear all digits that have been entered.
Central Station account: Each phone number has an account number associated with it. You may use a 3- or 4-
digit account number. If Ademco Contact I.D. is being used as the reporting format, a 4
digit account number must be used. The system allows additional characters as follows:
Hexadecimal Digit # or H Followed By
B1
C2
D3
E4
F5
Speak phone number: To confirm programmed phone numbers, Enter the appropriate 9000 location and the
number will be spoken. Special dialing feature codes will be heard as follows:
Dialing Feature Spoken As
Dial * Star
Dial # Pound
Wait for second dial tone Tone
3 second pause in dialing sequence Pause
Speak account number: Speaks programmed account number.
Echo communicator: To listen to the communicator transmission through the inside speaker, enter 9960 while
in program mode. Each communication will be heard over the inside speaker. When
testing is complete, return to programming mode and enter 9960 to turn off the
communicator monitor feature. Communicator monitor automatically turns off when
the panel is turned off or when the two-way voice circuit becomes active. Whenever
possible use the communicator monitor feature instead of a telephone butt set. The
panels phone circuit is very sensitive to loading. A good test to attempt when
experiencing communicator difficulties is to remove all connections from R1 and T1
and connect only the panel to R and T. This ensures a good phone connection and can
help isolate troublesome connections.
Communicator Time Options
Delay before dial: For both phone numbers, the system will wait a programmed time period (1 to 255
seconds) after activation before dialing the central station. If a value of 000 is
programmed, the communicator is disabled. If an alarm activation occurs and the
system is disarmed before the delay expires, the system will not communicate to the
central station. Valid delay values are 1-255 seconds.