System Times
System Time Options Time Increment Location Default
Entry delay 1 (Not to exceed 45 seconds in a UL installation)
...........................
seconds
..............
0136
.......
020
Entry delay 2 (Not to exceed 45 seconds in a UL installation)
...........................
seconds
..............
0137
.......
020
Exit delay (Not to exceed 60 seconds in a UL installation)
................................
seconds
..............
0138
.......
030
Alarm cut off and reset (Not to be less than 4 minutes in a UL installation)
.......
minutes
..............
0139
.......
005
* Duration between fire, tamper, trouble chirps
..................................................
seconds
..............
0142
.......
005
* Duration for recognition of AC power loss
.......................................................
minutes
..............
0153
.......
001
Time frame for User Test Timeout
.......................................................................
minutes
..............
0154
.......
003
Duration between spoken "Pre-alarm" cycles (000 = 3 seconds)
.........................
seconds
..............
0156
.......
000
Fire cut off and reset (Not permitted in a UL installation)
..................................
minutes
..............
0157
.......
005
Fire siren tone duration before speech
................................................................
seconds
..............
0158
.......
005
Burglary siren tone duration before speech
.........................................................
seconds
..............
0159
.......
005
Smoke verification smoke off duration before restore
(Must be 10 seconds in a UL installation)
...................................................
seconds
..............
0251
.......
005
Smoke verification smoke power restore duration
(Must be 25 seconds in a UL installation)
...................................................
seconds
..............
0252
.......
010
Smoke verification "window" delay duration
(Must be 120 seconds in a UL installation)
.................................................
seconds
..............
0253
.......
120
Number of 4 second samples to determine loss of phone line
........................................................
0456
.......
006
Answer service callback override wait time
.......................................................
seconds
..............
0470
.......
025
* 000 disables (Must be enabled for UL installation)
Automatic Arming and Disarming
This feature has not been evaluated for a UL installation
Options - Enter Total Location Value
Arm to AWAY
....................................................................................................................
001
Arm to HOME
...................................................................................................................
002
Disarm
...............................................................................................................................
008
Force arm with open zones
...............................................................................................
016
5 day cycle (otherwise 7 day cycle)
..................................................................................
032
Default (Automatic Arm / Disarm disabled)
..........................................
0169
...................
000
Monitor Trouble Conditions
Option Location Value
* High current (001 to enable)
...............................................................
0240
...................
001
* Monitor low battery and enable battery test (001 to enable)
..............
0241
...................
000
* Communicator fail (001 to enable)
.....................................................
0242
...................
000
* 000 disables (Must be enabled for UL installation)
Bypass Options
This feature is not permitted in a UL installation
Option - Enter Total Location Value
*{
Open zones automatically bypassed at force arm
..........................................................
001
Zones bypassed by force arm auto unbypassed at disarm
............................................... 002
Unbypass all bypassed zones automatically at disarm
......................................................
004
Default (Force Armed zones reactivated when shut)
............................
0243
...................
000
* These Bypass options are not available when Split Arming is enabled.
Time Options Time Increment Location Default
No. of activations before Auto-Bypass - 000 disables
........................................................
0176
.......
000
Time frame activations occur within
.....................................................
hours
...................
0177
.......
024