Editing Zone Programming
Once a zone has been programmed, the system provides a quick method for editing zone values. Enter 9,9,4,0
followed by the zone number. As each input prompt is played, press F1 and the system will replay the current
value. To change the configuration, enter a new value. To accept a current value, press F2. The Monitor button
will return to the previous prompt. The Monitor button will not return to prompts once the system has asked for F2
to confirm. Any changes made only take effect if the final question is answered and the system speaks exit.
Deleting a Zone
A zone can be deleted by entering a device type of 255.
Programming System Inputs to Zones Terms
System Input Automated Programming Locations
RF Strength Mode: This mode reduces the sensitivity of the receiver and speaks the serial number for all
5800 signals.
Exit Program Mode: Removes the system from program mode and places the system in keypad mode.
Zone Types
Exterior Instant: Exterior instant zones instantly sound an alarm when the system is armed to HOME,
AWAY or Night. When the system is not armed, monitor mode is active, and the zone
is programmed to show open/close status at the keypad, the system will speak the zone
description or sound a monitor beep when the zone input is activated. Exterior Instant
zones can be programmed to sound an alarm when the input is activated during an exit
delay (System Options - Group 2, option 008). Otherwise, the exterior instant zone will
respond in the same manner as when the system is not armed.
Exterior Delay #1: Tripping an exterior delay input places the system into a pre-alarm mode if the system is
armed to AWAY or HOME (unless "No entry delay for Exterior Delay #1 in Home" is
selected in System Options - group 2). The system refers to entry delay time #1 to
determine the pre-alarm duration. If pre-alarm expires without a user entering a valid
disarm code, the system will sound an alarm. When the system is not armed, monitor
mode is active, and the zone is programmed to show open/close status at keypad, the
system will speak the zone description or sound a monitor beep when the zone input is
activated. During an exit delay, Exterior Delay zones respond in the same manner as
when the system is not armed. In Night mode, this zone type acts an exterior instant.
Exterior Delay #2: Same as above but uses programmable entry delay time #2.
Interior Instant: The interior instant zones are active in the AWAY mode only. No monitor function is
provided for interior zones (except during extended monitor). During an exit delay, an
opening is ignored.
Interior Delay #1: Same as Exterior Delay #1 except active only in AWAY mode and no monitor is
provided.
Interior Delay #2: Same as Exterior Delay #2 except active only in AWAY and Night mode and no monitor
is provided. Uses delay time #2.
Fire: Fire zones respond with short high volume tones over the internal and external speakers.
The system will alternate between the tones and speaking "FIRE, FIRE," followed by the
up-to-four-word zone description, and "REMAIN CALM, LEAVE IMMEDIATELY."
Panic: Panic zones respond with a high volume alert on both the internal and external speaker.
The alert consists of a pulsed tone followed by "ALERT, ALERT", and the up-to-four-word
description of the zone.