AMX NXB-CCG-K Información técnica Pagina 88

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 87
88
Lutron® integration protocol
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 0–100 or
0.00–100.00
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Stop Lowering 3 None
Stop
Raising / Lowering
4 None
Start Flash
2
5 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Pulse 6 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Motor Jog Raise 18 None
Motor Jog Lower 19 None
Motor 4-Stage Jog Raise 20 None
Motor 4-Stage Jog Lower 21 None
NOTES
1. Fractions are rounded up to the closest ¼ second.
2. To stop a dimmer from flashing, send it to a valid level (action 1).
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 6, Action Number, Parameters
Remote Power Module (continued)
OUTPUT Commands
Vista de pagina 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 143 144

Comentarios a estos manuales

Sin comentarios