109
Lutron® integration protocol
Pico® Wireless Control (continued)
DEVICE Commands
DEVICE Command Formats
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
For all Legacy models and all Current models except for PJ2-4B
Button 1 2 Press, Release
Button 2 3 Press, Release
Button 3 4 Press, Release
Button Raise 5 Press, Release
Button Lower 6 Press, Release
For PJ2-4B model only
Button 1 8 Press, Release
Button 2 9 Press, Release
Button 3 10 Press, Release
Button 4 11 Press, Release
Action Numbers and Parameters:
Action Action Number Parameters
Press 3 None
Release 4 None
Example DEVICE Commands
Examples presume Pico® control has been assigned Integration ID 2.
Operation Command String
Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters
Press Button 1 (on a non-4B model). #DEVICE,2,2,3<CR><LF>
Response: ~DEVICE, Integration ID, Component Number, Action Number, Parameters
Button 1 was pressed. ~DEVICE,2,2,3<CR><LF>
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 2, Component Number, Action Number, Parameters
Comentarios a estos manuales