116
Lutron® integration protocol
Sivoia® QS Shade (continued)
OUTPUT Commands
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Zone Level 1 Level
1
= 0 –100 or 0.00 –100.00
2
Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
5
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising / Lowering
4 None
NOTES
1. For shades, a level of 0 (or 0.00) equals closed and a level of 100 (or 100.00) equals full open.
2. 0% = Closed; 100% = Open
3. Fade is not available for shades since they move at a constant rate. The parameter must be entered but is ignored.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a delay time is specified
as 1.45 seconds a value of 1.25 seconds will be used.
5. The Delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is
0.25seconds. The maximum delay time is 4 hours. Not supported in QS Standalone.
Example OUTPUT Messages
Examples presume shade has been assigned Integration ID 1.
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set shade to 75% with a 1 min 30 sec delay. #OUTPUT,1,1,75,0,1:30<CR><LF>
Start Raising shade level. #OUTPUT,1,2<CR><LF>
Stop Raising / Lowering shade level. #OUTPUT,1,4<CR><LF>
Query: ?OUTPUT, Integration ID, Action Number
What is the state of the output? ?OUTPUT,1,1<CR><LF>
Response
1
: ~OUTPUT, Integration ID, Action Number, Parameters
Output level is set to 90%. ~OUTPUT,1,1,90.00<CR><LF>
NOTE
1. The system will report the target level of a shade. The actual level is not transmitted while they are moving.
Example: If the Living Room Blackouts (Integration ID 1) are at 20% and are commanded to go to 100% by sending
#OUTPUT,1,1,100 the response from the system will be ~OUTPUT,1,1,100.00
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 1, Action Number, Parameters
Comentarios a estos manuales