AMX NXB-CCG-K Información técnica Pagina 55

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 144
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 54
55
Lutron® integration protocol
Example OUTPUT Messages
Operation Command String
Execute: #OUTPUT, Integration ID, Action Number, Parameters
Set output level to 70% (Fade = 4 sec, Delay = 2 sec) #OUTPUT,2,1,70,4,2<CR><LF>
Raise Output #OUTPUT,2,2<CR><LF>
Query: ?OUTPUT, Integration ID
What is the current output level? ?OUTPUT,2<CR><LF>
Response: ~OUTPUT, Integration ID, Action Number, Parameters
1
Output level is set to 48%. ~OUTPUT,2,1,48<CR><LF>
NOTE
1. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second
delay. The minimum fade and delay time is 0 seconds. The maximum fade and delay time is 4 hours. For shade outputs,
the Fade parameter has no effect (since shades have fixed speeds) but it is required when specifying an optional delay.
Quantum® (continued)
System Commands (continued)
OUTPUT Commands (continued)
Vista de pagina 54
1 2 ... 50 51 52 53 54 55 56 57 58 59 60 ... 143 144

Comentarios a estos manuales

Sin comentarios