Lutron® integration protocol
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB
RadioRA® 2 (continued)
Integration Access Points (continued)
Connection Information
Provides an RS232 and Ethernet connection to communicate with external equipment.
RS232
The RS232 connection has the following communication settings:
• Baud Rate 9600
• 8 data bits
• No parity bit
• 1 stop bit
• No flow control
Ethernet
Configuring the control interface to communicate over a network takes not only knowledge of
the RadioRA® 2 system, but of networking as well. Installers with limited networking knowledge
are advised to contact a networking professional before attempting to connect a control interface
through a network. The information below will help an installer communicate the control interface
configurations to a network professional.
The installer will make any necessary changes to the control interface using the Lutron® DeviceIP
or RadioRA® 2 PC software tool and the network professional can make any necessary changes to
the networking equipment.
Single Ethernet Port
• IEEE® 802.3 Auto-Sensing 10BaseT / 100BaseTX
• Supports MDI/MDIX auto-crossover (no crossover cable needed).
• Female 8P8C “Computer RJ-45” socket
• Green “Connect” LED, Amber “Activity” LED
• Use Cat 5 cabling or better
TCP / IP Settings
• DHCP (dynamic) or static configuration <factory default = DHCP>
• IP Address: <static default = 192.168.1.50 or dynamic configuration>
• Subnet Mask: <static default = 255.255.255.0 or dynamic configuration>
• Gateway: <static default = 0.0.0.0 or dynamic configuration>
Protocols Used for Integration
• TELNET
Telnet Server
• Up to 4 telnet sessions can be accessed through Essentials Software
• Used by software and/or third party equipment (e.g., touch screen)
• Limited to transferring ASCII characters
• Login: lutron
• Password: integration
Notes:
– Up to four additional login and password values can be defined in the RadioRA® 2 PC software.
– Only one connection per login / password is allowed at a time.
UDP Multicast Messaging
• Used by the RadioRA® 2 PC software during device configuration and system programming
• There are no user modifiable settings for UDP messaging