AMX AXD-CP4/PB Especificaciones Pagina 257

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 364
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 256
Design Ver. 0002 DS - 15
4. Use the following sheet to calculate the input transformer, and the section of the
mains cables.
Rated current through
the mains cable:
x
=
Amp
< 12.2
< 16.5
< 23
< 29
< 40
< 53
< 67
< 83
Power Cable
Reference
MPC-4x1.5
MPC-4x2.5
MPC-4x4
MPC-4x6
MPC-4x10
MPC-4x16
25 mm
2
(MPC-4x25 + (2x1))
35 mm
2
(MPC-4x35 + (2x1))
Power Supply
Axis Compact Module (ACD):
The length of these power cables must
be specifically ordered (in meters).
(kW) (Amp)
Power cables for mains connection
4
FXM Motor Rated Current
=
(Amp)
Spindle Compact Module (SCD):
Maximum SPM Motor Current
=
(Amp)
1000
Vmains 3
Vmains = From 380 to 460 Vac.
Transformer:
The transformer or autotransformer being used must be of the power:
Very important:
when using an isolation transformer, the secondary must be of the star type its mid point being accessible so
it can be connected to ground.
Mains voltage
The Fagor Servo Drive system requires 380-460 Vac.
1 2 ( + ) 1.05 (kW) = (kW) 4x
Vista de pagina 256
1 2 ... 252 253 254 255 256 257 258 259 260 261 262 ... 363 364

Comentarios a estos manuales

Sin comentarios