OFPC Project No. 703-039 M.D. ANDERSON CANCER CENTER
Ambulatory Clinical Building
55050.00
AV BID AUDIO VISUAL SYSTEM
03/11/04 11738 -14
and destination routing assignments, audiovisual system power (including projector power), and VCR
transport functions. Include screen design and menu branching drawings in submittals. Provide new,
install in AV rack, and integrate into system as shown in drawings. Install new and integrate into system
as shown in drawings.
G. Connectors – Connectors to be of the quantity and type as required for proper and durable operation
and signal transmission of the electrical characteristics for associated circuitry. Microphone connectors:
3-conductor XLR type. Control panels: XLR type with number of conductors as required. Line level and
left/right audio connectors: tip/ring/sleeve 1/4” phone jacks with insulated bushings. Composite video
and RGBS connectors: BNC dual crimp 75 ohm Canare or accepted substitution. S-video: standard 4-
pin S-video mini-din.
H. Interconnect Wiring – Provide and install following cable as required for connections in all areas. Meet
provisions of N.E.C.
Audio Plenum Rated Cable: West Penn 25452, West Penn 25291, or similar.
Composite Video Plenum Rated Cable: West Penn 25806
RGBHV Plenum Rated Cable: West Penn 258195 or Belden 1826A or Liberty RGB5C-SD-PLN.
Control Plenum Rated Cable: Control Plenum Rated Cable: West Penn D25350
Control CAT5E Plenum Rated Cable: West Penn 254245
Loudspeaker plenum cable: West Penn 25226
I. Multi-Media Lectern Video Switcher (VSW-10) – Extron MAV44AV (quantity: 1) four input, four output
composite video with balanced stereo audio matrix switcher. Provide new, and integrate into system as
shown in drawings.
J. Multi-Media Lectern EtherNet Switch – Cisco Catalyst 2940-8TT fast Ethernet switch. Provide new, and
integrate into system as shown in drawings.
K. Multi-Media Lectern Integrated Control System (LIC-1) – AMX NI-2000 integrated control system.
(quantity: 1). AMX to provide all software programming. Refer to AMX Master Quote #M40031. Owner
to provide a copy of standard Touch Panel pages for reference. AV Contractor to provide all source
code. AV Contractor to provide web-control using AMX NetLinx controller internal web interface.
Provide web-control for each Touch Panel in AV system. Include page tracking between Touch Panel
and web-control panel. Also include in submittals a detailed one-line diagram of control system network
configuration showing all interface boxes, power supplies, Ethernet hubs etc. Provide new and install
with rack mount kit in Lectern racks and integrate into system as shown in drawings.
L. Multi-Media Lectern Cable Cubby (LCC-1) – Extron 300 Series Cable Cubby (quantity: 1) with
cables/connectors as shown in drawings. Provide new, install in lectern rack and integrate into system
as shown in drawings.
M. Multi-Media Lectern Rack Drawer (DRAW-L1) – Middle Atlantic TD2-FLK two rack unit lockable drawer
(quantity: 1). Provide new, install in lectern rack and integrate into system as shown in drawings.
N. AMX Control Power Breakout Cable- Provide six foot power breakout cable with 4-pin XLR to mini
phoenix connector (quantity: 2). Provide new.
2.7 AV RACK PRODUCTS – TELEMED / MULTI DISC ROOM 1.2360B
A. AV Rack Electrical Power - Coordinate with Electrical Contractor regarding proper placement of isolated-
ground duplex outlets on walls of the AV Booth Area. Electrical circuits should be connected (and
outlets wired) by the Electrical Contractor to the AV system circuit breaker panel (N.I.C.). Ensure that
“Star” ground configuration is properly implemented by the Electrical Contractor. Ensure that ground