Rosemount 3300 Series
October 2014
www.rosemount.com
Product Certifications
Safety note
A safety isolator such as a zener barrier is always needed for intrinsic
safety.
Probes covered with plastic and/or with plastic discs may generate an
ignition-capable level of electrostatic charge under certain extreme
conditions. Therefore, when the probe is used in a potentially explosive
atmosphere, appropriate measures must be taken to prevent
electrostatic discharge.
EU Conformity
The most recent revision of the EC declaration of conformity can
be found at www.rosemount.com.
Hazardous locations certifications
North-American certifications
Factory Mutual (FM) Approval
Project ID: 3013394
E5 Explosion-proof for use in Class I, Div. 1,
Groups B, C, and D;
Dust-ignition-proof for use in Class II/III,
Div. 1, Groups E, F, and G;
With Intrinsically Safe connections to Class I, II, III, Div. 1,
Groups A, B, C, D, E, F, and G.
Temperature Class T5 @ +85 °C.
Ambient temperature limits -50 °C to +85 °C.
Approval valid for HART and Modbus options.
I5 Intrinsically Safe for Class I, II, III, Div. 1,
Groups A, B, C, D, E, F, and G,
Class I, Zone 0, AEx ia IIC T4 Ta=70 °C.
Temp code T4 at 70 °C max ambient.
Installation Drawing: 9150077-944.
Non-Incendive Class I, Div. 2, Groups A, B, C, and D;
Suitable for Class II, III, Div. 2, Groups F and G.
Non-incendive maximum operating
parameters: 42 V, 25 mA.
Temp code T4A at 70 °C max ambient.
Approval valid for HART option.
Canadian Standards Association (CSA) Approval
Certificate: 1250250.
E6 Explosion-proof: Class I, Div. 1, Groups C and D.
Dust Ignition Proof:
Class II, Div. 1 and 2, Groups G and coal dust.
Class III, Div. 1, Haz. Loc.
[Ex ia IIC T6].
Ambient temperature limits -50 °C to +85 °C.
Approval valid for Modbus and HART option.
I6 Intrinsically Safe: Ex ia IIC T4,
Class I, Div. 1, Groups A, B, C, and D.
Temp code T4.
Installation Drawing: 9150077-945.
Non-Incendive: Class III, Div. 1, Haz. Loc.
Class I, Div 2, Groups A, B, C, and D.
Ambient temperature limits -50 °C to +70 °C.
Approval valid for HART option.
European certifications
ATEX Approval
E1 Flameproof:
Certificate: KEMA 01ATEX2220X
0575
II 1/2 G Ex d [ia Ga] IIC T6...T1 Ga/Gb
II 1/2 D Ex tb [ia Da] IIIC T85 °C...T450 °C Da/Db
(1)
or
II -/2 D Ex tb IIIC T85 °C...T135 °C -/Db
U
m
= 250 V
Ambient temperature range: -50 °C
(2)
to +75 °C
Approval valid for HART and Modbus options.
Special Conditions for Safe Use (X):
1. On application of the transmitter with plastic covered
probes, in an explosive gas atmosphere, precaution shall
be taken to avoid danger of ignition due to electrostatic
charges on the probe.
2. On application of the transmitter in an explosive dust
atmosphere, the transmitter shall be installed in such a
way that the risk from electrostatic discharges and
propagating brush discharges caused by rapid flow of dust
at the label is avoided.
3. For probes and flanges containing light metals, an ignition
hazard due to impact or friction needs to be avoided
according to IEC 60079-0 clause 8.3, when used as EPL
Ga/Gb equipment.
(1) Non-plastic covered probes only
(2) -40 °C for process temperature range -196 °C to -50 °C
Table 13. Process Temperature Limits
Maximum ambient
temperature (°C)
Maximum process
temperature (°C)
Temperature class/
maximum surface
temperature
+75 +75 T6 / T 85 °C
+75 +90 T5 / T 100 °C
+75 +125 T4 / T 135 °C
+75 +190 T3 / T 200 °C
+65 +285 T2 / T 300 °C
+55 +400 T1 / T 450 °C