www.rosemount.com
External Power Supply
The input voltage (U
i
) for HART is 11 to 42 Vdc
(11 to 30 Vdc in IS applications, and 16 to 42 Vdc
in Explosion-proof/Flameproof applications).
For Flameproof/Explosion-proof installations the
Rosemount 3300 Series transmitters have a
built-in barrier; no external barrier needed.
When a Smart Wireless THUM adapter is fitted,
it adds a maximum drop of 2.5 Vdc in the
connected loop.
R = Load Resistance (); U
E
= External Power
Supply Voltage (Vdc); and U
I
= Input Voltage (Vdc)
IS Electrical Parameters U
i
= 30 V, l
i
= 130 mA, P
i
= 1 W, L
i
= 0, C
i
= 0
Signal on Alarm Standard: Low = 3.75 mA. High = 21.75 mA; Namur NE43: Low = 3.6 mA. High = 22.5 mA
Saturation Levels Standard: Low = 3.9 mA. High=20.8 mA; Namur NE43: Low = 3.8 mA. High = 20.5 mA
Load Limitations
Maximum load resistance is determined by the voltage level of the external power supply, as
described by:
11
400
800
1200
1600
20 30
40
50
4224
650
1550
400
800
1200
1600
11 20 30 40 50
950
650
24
R ()
U
E
(V)
R ()
U
E
(V)
Operating
Region
U
E
=External Power Supply Voltage; R () = Maximum Load Resistance
11 20 30 40 50
400
800
1200
1600
1300
16
24 42
U
E
(V)
R ()
Operating
Region
Non-Hazardous Installations Intrinsically Safe Installations
Explosion-proof/Flameproof
(Ex d) Installations
Note
For the Ex d case, the diagram is only valid if
the HART load resistance is at the + side,
otherwise the load resistance value is limited
to 300