Chapter 5 Parameters|VFD-B Series
5-34 Revision July 2008, BE16, SW V4.08 & V5.00
Group 2: Operation Method Parameters
02 - 00 Source of First Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs
UP/DOWN. Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
05 RS-485 serial communication (RJ-11). Last used frequency not
saved.
06 Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
02 - 13 Source of Second Master Frequency Command
Factory Setting: 00
Settings 00 Digital keypad UP/DOWN keys or Multi-function Inputs UP/DOWN.
Last used frequency saved.
01 AVI 0 ~ +10VDC
02 ACI 4 ~ 20mA
03 AUI -10 ~ +10VDC
04 RS-485 serial communication (RJ-11). Last used frequency saved.
05 RS-485 serial communication (RJ-11). Last used frequency not
saved.
06 Combined use of master and auxiliary frequency command
See Pr. 02-10 to 02-12
These parameters set the Master Frequency Command Source of the AC motor drive.
02 - 01 Source of First Operation Command
Factory Setting: 00
Settings 00 Digital keypad (PU01)
01 External terminals. Keypad STOP/RESET enabled.
02 External terminals. Keypad STOP/RESET disabled.
03 RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
04 RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.