Appendix C How to Select the Right AC Motor Drive|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 C-3
The
requirement
of load capacity should be less than the capacity of AC
motor drive(kVA)
The requirement of load capacity=
)(_____
cos
kVAdrivemotorACofcapacitythe
Pk
M
×
×
ϕη
The motor capacity should be less than the capacity of AC motor drive
)(_____103
3
kVAdrivemotorACofcapacitytheIVk MM ××××
The current should be less than the rated current of AC motor drive(A)
)(______ AdrivemotorACofcurrentratedtheIk M ×
Symbol explanation
M
P
: Motor shaft output for load (kW)
η
: Motor efficiency (normally, approx. 0.85)
ϕ
cos
: Motor power factor (normally, approx. 0.75)
MV
: Motor rated voltage(V)
M
I
: Motor rated current(A), for commercial power
k
: Correction factor calculated from current distortion factor (1.05 - 1.1, depending
on PWM method)
1CP
: Continuous motor capacity (kVA)
Sk
: Starting current/rated current of motor
Tn
: Number of motors in parallel
Sn
: Number of simultaneously started motors
2
GD
: Total inertia (GD
2
) calculated back to motor shaft (kg m
2
)
L
T
: Load torque
A
t
: Motor acceleration time
N : Motor speed
Vista de pagina 233