Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-103
11 - 05 Sleep/Wake Up Detection Time Unit: 0.1
Settings 0.0 to 6550.0 sec Factory Setting: 0.0
11 - 06 Sleep Frequency Unit: 0.01
Settings 0.00 to Fmax Hz Factory Setting: 0.00
11 - 07 Wakeup Frequency Unit: 0.01
Settings 0.00 to Fmax Hz Factory Setting: 0.00
When the actual output frequency
Pr.11-06 and the time exceeds the setting of Pr.11-05,
the AC motor drive will be in sleep mode.
When the actual frequency command > Pr.11-07 and the time exceeds the setting of Pr.11-05,
the AC motor drive will restart.
When the AC motor drive is in sleep mode, frequency command is still calculated by PID.
When frequency reaches wake up frequency, AC motor drive will accelerate from Pr.01-05 min.
frequency by V/f curve.
The wake up frequency must be higher than sleep frequency.
11-07
11-06
01-08
01-05
11-05
Frequency
The limit of
decel. time
frequency calculated by PID
output
frequency
Time
The limit of
accel. time
Fmin
Fsleep
Fcmd=0
Fout = 0
lower bound
of frequency
Fmin<Fsleep<
lower bound
of frequency
Vista de pagina 159