Lutron® integration protocol
NOTES
1. AREA can only be used to control areas of a QuantumR system that have been assigned to a particular
integration access point. Please refer to the Q-DesignT software (Integration Tab) or QuantumR Integration
Report for details of what areas are available for control and monitoring.
2. AREA commands cannot be sent to areas that contain other areas, such as a floor or an entire building.
3. The Level is accepted as a percentage.
4. The Fade and Delay time are optional. When not used the system will use a one second fade time with zero
second delay. The minimum fade and delay time is 0 seconds. The maximum fade and delay time is 4 hours.
5. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time
is specified as 1.45 seconds a value of 1.25 seconds will be used.
6. When a Raise / Lower command is issued, the area’s level will continue to go towards high end / low end until
a Stop command is received.
7. Scene 0 is the Off Scene.
8. If After Hours is used in an area, setting the area’s Occupancy Mode to “Occupancy and Vacancy” or
“Vacancy” will activate After Hours.
9. The area will report “Not Applicable” as its Occupancy Mode if the area does not have occupancy sensors
and if After Hours is not used.
Quantum® System Commands (continued)
QSE-CI-NWK-E: AREA Commands (continued)