AMX NXB-CCG-K Información técnica Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 137
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
12
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 0–100 or
0.00–100.00
SS.ss
2
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising / Lowering 4 None
Start Flash
3
5 SS.ss
2
, SS, MM:SS, or HH:MM:SS
Pulse 6 SS.ss
2
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
4,8
Venetian tilt level only
9 Tilt Level
1
= 0 –100 or 0.00 –100.00
1
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
8
Venetian lift & tilt level
10 Lift Level
1
= 0 –100 or 0.00 –100.00
1
Tilt Level
1
= 0 –100 or 0.00 –100.00
1
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
4
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Start raising Venetian tilt
11 None
8
Start lowering Venetian tilt
12 None
8
Stop Venetian tilt
13 None
8
Start raising Venetian lift
14 None
8
Start lowering Venetian lift
15 None
8
Stop Venetian lift
16 None
8
Set DMX color / level settings
5
17 Color / level index: 0 –255
0.00–100.00
6
Lutron® integration protocol
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 6, Action Number, Parameters
Integrator's Reference (continued)
OUTPUT: Command Summary
Outputs are dimmers, CCOs, or other devices in a system that have a controllable output. All of these
devices will accept levels from 0% to 100% and 0.00% to 100.00% with a given fade and delay time.
These same commands can be monitored in real-time as they occur in the system.
Continued on next page…
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 136 137