Programming
22
ViewStat Color Communicating Thermostat
AxLink Commands
This section contains AxLink commands that are specific to the ViewStat Color Thermostat. For
additional AxLink programming commands specific to a particular AxLink device, consult the manual
for the AxLink device you are using.
AxLink Commands
BK
Sets the backlight
timeout value and
active and
inactive
brightness.
Syntax:
BK [T<SEC>] [A<ABVAL>] [I<IBVAL>]
Variable:
SEC = An integer with a value between 10 and 300 in values evenly divisible by 10.
ABVAL = A single character with a value of L, M, or H, where L=Low, M=Medium, and
H=High
IBVAL = A single character with a value of D or O, where D=Dim and O=Off
Example:
SEND_COMMAND ’BK T20 IO’
Sets the timeout to 20 seconds and Inactive Brightness to OFF.
SEND_COMMAND ’BK T10 AL’
Sets the timeout to 10 seconds and Active Brightness to ON.
CD
Retrieves and
sets the security
code
configuration.
Syntax:
CD <Code>
Variable:
Code = A 4-character integer.
Example:
SEND_COMMAND ’CD 1988’
Changes the security code to 1988.
CF
Displays the
current forecast.
Syntax:
CF F<Temp> W<Direct> S<Speed> H<HRead> D<DewPT>
Variable:
Temp = The wind chill or heat index that denotes what the temperature feels like outside.
The temperature is reported in the same scale as set on the thermostat: Fahrenheit (F)
or Celsius (C).
Direct = A single character noting the wind direction (N, S, E, or W).
Speed = The wind speed in either miles per hour (mph) or kilometers per hour (kph),
depending on the temperature scale.
HRead = The current percent humidity reading with a range of 0 to 100%.
DewPT = The current dew point temperature reported in the same scale as set on the
thermostat: F or C.
Example:
SEND_COMMAND ’CF F40 WN S25 H35 D55’
Reports the forecast as Wind Chill: 40F, Wind Direction: North, Wind Speed: 25 mph,
Humidity: 35%, Dew Point: 55F.