Section 7 – Displaying and Responding to Profit Optimizer Messages
7.4 Dictionary of Profit Optimizer Messages
84 Profit Optimizer User's Guide 1/00
Honeywell Inc.
Profit Optimizer Messages
1 - 6
1
Message: Illegal CDS type
Error
Meaning Suggested Response
Controller requested pointer for interface CDS other than
CV, MV, DV, BDVs DQP-side interface point DMOD_CDS,
DIN_CDS, DOUT_CDS.
Call the Honeywell Technical Assistance Center.
2
Message: Max DQP points per AM exceeded
Error
Meaning Suggested Response
Attempt to install more controllers on the AM than are
allowed – out of graphic space.
Delete obsolete controllers, or build new
controller in a different AM.
3
Message: Total number of CVs out of range
Error
Meaning Suggested Response
Violation of an integrity check. Total number of CVs is
greater than:
400 minus number of combined constraints on the AM;
800 minus number of combined constraints on the AxM.
Ensure that number is in the correct range.
4
Message: Total number of MVs out of range
Error
Meaning Suggested Response
Violation of an integrity check. Total number of MVs is
either greater than:
200 on the AM; 400 on the AxM.
Ensure that number is in the correct range.
5
Message: Total number of DVs out of range
Error
Meaning Suggested Response
Violation of an integrity check. Total number of DVs is
either greater than:
200 on the AM; 400 on the AxM.
Ensure that number is in the correct range.
6
Message: Could not get point info ($setup)
Error
Meaning Suggested Response
Controller could not get information for control point. Call the Honeywell Technical Assistance Center.