LRC1010, LRC1015 datasheet
TRIOS, multi-functional light controller, switching
2/6
Applications
• Applicationscanrangefromoffices(corridors,lobbies,etc.Fordesk
area’stheOccuSwitchrangeismoresuitable),schools(corridors,
playingareas,halls,etc.ForclassroomstheOccuSwitchrangeismore
suitable),industry(distributioncenters(aspecificapplicationsheetis
available))andretailbuildings.
• Lightscanbecontrolledaccordingto:
• manuallightswitchingwithaninfraredreceiverandtransmitter,•
manuallightswitchingwithstandardpushbuttonsconnectedtothe
LCU8020pushbuttoninterfaceunit.
• manuallightswitchingwithapush-buttonconnectedtothedigital
input(‘toggle’switching).
• automaticlightswitchingbyalightsensorwhichmonitorsthe
ambientlightlevel.
• automaticlightswitchingbyamovementdetectorwhichmonitors
theoccupancyinadefinedarea.
• Sensorcablesareusedtoconnectsensorstothelightcontrollersor
toincreasethedistancebetweenthesensorandcontroller.
• ThemaximumcablelenghtbetweenasensorandtheTRIOSunitis
30meters.
• Thesumofsensorcablelengthsmaynotexceed125mwithupto
twoTRIOSunitslinkedtogether,100mwith3or4TRIOSunitsand
85mwith5TRIOSunits.
• AfunctionalcontrolprogrammeinTRIOSdetermineshowthelights
areswitched.Theconnectedsensorconfigurationautomatically
determinestheselectedcontrolprogramme.
• Allparameterswithinthiscontrolprogrammearefixed.
• WiththeOmniProgIRT8099/10thegroupandchanneladdresscan
bechanged.
• Sensorsignalstoonecontrollercanbepassedtoamaximumoffour
othercontrollersbyinterlinkingthecontrollersviathemodularinput
sockets.Alimitednumberofsensorscanthereforecontrollarger
loads(upto25A).Eachcontrollerhastobeconnectedtomainsand
luminaires.
Functionality
Address programming
ThegroupandchanneladdressesoftheTRIOScanbechangedusing
theOmniProgIRT8099/10.Asprogrammingmustbeaselectiveaction,
theTRIOSprogrammingtoolhasareducedIRradiationandmustbe
carefullypointedattherelevantreceiver.Eachsuccessfulprogramming
actionisconfirmedbyTRIOSbyashortflashoftheconnectedlights.
Sensors
General.
TRIOSdetectswhichsensorsareconnectedandactivated,and
automaticallyadaptsitsfunctionalitytothefoundconfiguration.
Thetablebelowgivesafullsurveyforthevarioussensorsandtheir
combinations.
Push-button interface
Insteadof,orincombinationwith,theinfraredreceiver,thepushbutton
interfaceLCU8020canbeconnected.Push-buttonsconnectedtothe
LCU8020canbegiventhesamefunctionsastheinfraredtransmitters,
butalsoothercombinationsarepossible.Maximum19pushbuttons
canbeconnected.Functionsrealisedinthiswayfollowtherulesforthe
infraredreceiveraslistedinthetablebelow.Forinstance:dimmingof
channelsandtheselectionofpresetsisdisabledifapotentiometeris
connected.
TheTRIOSsystemcanbeusedwiththePhilipsLRM8xxxmovement
detectors(normalheightandhighbay),theIRR801xIRreceivers,the
LRI8102highbaylightsensorortheLRI813xmultisensors(fornormal
heights).Inthelastcaseitispossibletouseonlyoneortwoofthe
threesensorfunctions.
Light Sensor
Whenallowedbyothersensorsthatarepossiblyconnected,theLight
SensorwillswitchonTRIOSwhenthemeasuredlightleveldropsbelow
theswitchonlevel(4voltsatthesensoroutput).
WhentheLightSensorisused,theluxlevelonaworkingsurfacewill
beapproximately600lux,whentheaveragesurfacereflectioninthe
roomis30%.Otherluxlevelsareobtainedwithdifferentreflection
coefficients.
Thedesiredluxlevelcanbechangedbyadjustingthelightsensitivity
ofthesensor(changeitspre-adjustedsensitivityusingthetrimming
potentiometer).
TRIOSwillswitchoffwhenthemeasuredluxlevelremainsabove
theswitchofflevelformorethan15minutes.(8.8Voltsatthesensor
output).
Telejack connectors
AWG 26
1
2
3
6
5
4
RJ-12 (6p / 6c)
6 5 4 3 2 1
1 2 3 4 5 6
Pin/core
1
2
3
4
5
6
Colour wire
White
Black
Red
Green
Yellow
Blue
Function
+12 Vdc
GND
+5 Vdc
IR
RC5
1
2
3
6
5
4
Notes:
• WhenaReferenceLevelissettoohigh(correspondingtomorethan
4Vdcatthelightsensorinput),theswitch-offlevel(>10Vdcatthe
lightsensorinput)cannotbereached.
• Whenthelightsensorisusedwithoutaninfraredreceiverora
potentiometer,the(default)luxlevelonaworkingsurfacewillbe
600lux,whentheaveragesurfacereflectioncoefficientintheroom
is30%.Otherluxlevelsareobtainedwithdifferentreflection
coefficients.