SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242i 3 03.27.15
Specifications
QS Sensor Module (QSM)
Power
• 24 V
• Current draw:
max 400 mA (models with wired input)
max 100 mA (models without wired input)
• Power Draw Units: (PDU)
Refer to the QS Link Power Draw Units specification
submittal (LutronR P/N 369405) for information concerning
PDUs on the QS Link. Use only LutronR approved power
sources.
• 10-year power failure memory: restores settings and
programming after power interruption.
Regulatory
• LutronR Quality Systems registered to ISO 9001.2008.
QSM2 –
• cUL US Listed (USA and Canada).
•
FCC Compliant. Complies with the limits for a Class B
digital device, persuant to Part 15 of the FCC Rules (USA).
• IC Certified. (Canada).
• SCT Certified (Mexico).
QSM3 –
• CE Marked (European Union).
• TRA Type Approved (United Arab Emirates).
QSM5 –
• WPC Type Approved (India).
QSM7 –
•
FCC Compliant. Complies with the limits for a Class B
digital device, persuant to Part 15 of the FCC Rules (USA).
Environment
• Ambient Temperature Operating Range: 32 ºF to 104 ºF
(0 ºC to 40 ºC).
• Relative humidity: less than 90% non-condensing.
• For indoor use only.
Terminals
• Input wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
• QS link wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
Mounting
• QSM units should be mounted in the middle of non-
metal ceiling tile or drywall, visible from inside the space.
• Installation near metal other than a Junction Box may
reduce RF range.
Wireless Communication
(models with wireless inputs only)
• RF Range: 60 ft (18 m) line of sight, or 30 ft (9 m)
through typical construction materials.
• To ensure optimal wireless range, install the QSM in
the ceiling in a visible position from inside the space.
• LutronR Radio Powr SavrTM Occupancy sensor
(up to 10)
• LutronR Radio Powr SavrTM daylight sensor (up to 10)
• LutronR PicoR wireless controllers (up to 10)
Wired Inputs
• There are 4 universal wired inputs. Each input can
accept one of the following:
- LutronR EcoSystemR wallstations
- LutronR occupancy sensors (LOS- series)
- LutronR daylight sensors (EC-DIR- series)
- LutronR EcoSystemR infrared (IR) receivers (EC-IR,
EC-DIR- series)
- LutronR Wired PicoR Controls
• Use of both the infrared receiver and daylight sensor
on the EC-DIR- series sensors is considered two
wired inputs on a QSM
• Maximum wiring distance = 150 ft (46 m)
QS Link Limits
• The QS link can have up to 100 devices.
• Each QSM counts as 1 device towards the
100 device limit.
• Each QSM draws 3 Power Draw Units (PDUs) on
the QS link.
• Wired sensors add to the PDU draw of a QSM.
Refer to the QS Link Power Draw Units specification
submittal (LutronR P/N 369405) for information
concerning PDUs.
• QS link maximum wire run length is 2000 ft (610 m).