STEP 7
R
16 Installation of GRAFIK5000 / GRAFIK6000 / GRAFIK7000 System
Each device along the Control Station Device
(CSD) Link must have a unique address
ranging from 1 to 32. The Address Switches
may have been pre-set to give the address
shown on the job drawings.
Set Control Station Device Address Switches
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
9
10
11
12
13
14
15
16
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1234567
ON
1
2
3
4
5
6
7
8
Address Switch Settings Chart - shows how to
set the Address Switches to get a specific
address.
Notice!
Do not install a CSD without confirming
that the Address Switches have been
set.
If the Address Switches were not pre-set (all
set to address 1), assign each CSD a unique
address and document its location and
description.
If needed, refer to the instructions for each
CSD to help locate its Address Switches.
2B3
Job drawings may show:
Address 3 ...
on CSD Link B ...
in Processor 2
(omitted if only one processor)
Note
GRAFIK Eye
® Control Units (GRX-46xx-x-xx) do
not have Address Switches but must be
programmed with a unique address(es). See
separate instructions sent with each Control
Unit.