Examples of RS232 communications could involve another Red Lion
product or a PC. By using a cable with RJ12 ends on it, and a twist in the cable,
RS232 communications with another G3 product or the Modular Controller can
be established. Red Lion part numbers for cables with a twist in them are
CBLPROG0
1
, CBLRLC01
2
, or CBLRC02
3
.
G3 RS232 to a PC
Connections
G3: RJ12 Name PC: DB9 Name
4 COMM 1 DCD
5 Tx 2 Rx
2 Rx 3 Tx
N/C 4 DTR
3 COMM 5 GND
N/C 6 DSR
1 CTS 7 RTS
6 RTS 8 CTS
N/C 9 RI
1
CBLPROG0 can also be used to communicate with either a PC or an ICM5.
2
DB9 adapter not included, 1 foot long.
3
DB9 adapter not included, 10 feet long.
RS422/485 COMMS PORT
The G310 has one isolated RS422/485 port. This port can be configured to
act as either RS422 or RS485.
Note: All Red Lion devices connect A to A and B to B, except for Paradigm
devices. Refer to www.redlion.net for additional information.
5
OFF 4 WIRE/ ON 2 WIRE
OFF 4 WIRE/ ON 2 WIRE
*
*
*
*
*
*
*
*
*
*
9
PULL UP
PULL DOWN
115200 BAUD
57600 BAUD
38400 BAUD
19200 BAUD
9600 BAUD
2
1
5
3
4
7
8
6
OFF DCE/ ON DTE
OFF DCE/ ON DTE
OFF DTE/ ON DCE
OFF 422/ ON 485
OFF 422/ ON 485
OFF DTE/ ON DCE
120Ω TERMINATION
5
NC
10
1
3
2
4
6
7
ON
ON
CBLPROG0
ICM5
CONNECTING A G310 OPERATOR
INTERFACE TO AN ICM5
*
Application Dependent
ICM5 DIP Switch Settings
Examples of RS485 2-Wire Connections
G3 to Red Lion RJ11 (CBLRLC00)
DLC, IAMS, ITMS, PAXCDC4C
Connections
G3: RJ45 Name RLC: RJ11 Name
5 TxEN 2 TxEN
6 COMM 3 COMM
1 TxB 5 B-
2 TxA 4 A+
G3 to Modular Controller (CBLRLC05)
Connections
G3 Name Modular Controller Name
1,4 TxB 1,4 TxB
4,1 RxB 4,1 RxB
2,3 TxA 2,3 TxA
3,2 RxA 3,2 RxA
5 TxEN 5 TxEN
6 COMM 6 COMM
7 TxB 7 TxB
8 TxA 8 TxA
DH485 COMMUNICATIONS
The G310’s RS422/485 COMMS port can also be used for Allen Bradley
DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect this port to
Allen Bradley equipment. A cable and wiring diagram are available from
Red Lion.
G3 to AB SLC 500 (CBLAB003)
Connections
RJ45: RLC Name RJ45: A-B Name
1 TxB 1 A
2 TxA 2 B
3, 8 RxA - 24V
4, 7 RxB - COMM
5 TxEN 5 TxEN
6 COMM 4 SHIELD
4, 7 TxB - COMM
3, 8 TxA - 24V
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
GND
6
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 GND
RS422/485 4-WIRE
CONNECTIONS
RS485 2-WIRE
CONNECTIONS
ISOLATED
ETHERNET
AUXILIARY
ISOLATED
RS232
PORT B
E F
ETHERNET
ISOLATED
D
B C
A
HOST B
A
PGM PORT
ISOLATED
RS232
PORT A
ISOLATED
-
+
24VDC
SUPPLY
PORT A
RS485
A
POWER
PROGRAMMING
HOST A
A
USB DEVICE
POWER SUPPLY ISOLATION BLOCK DIAGRAM
Comentarios a estos manuales